Moeller ZM-16-PKZ2 trip module with an adjustable trip from 10-16 AMPS. Note this is ONLY the trip module. A PKZ2 Starter base is needed to form a complete starter unit.
Product Specifications
Product Attribute | Attribute Value |
Each trip module has a coordinated, independently adjustable, over-current trip (yellow dial) for overload protection (0.6 -1.0 x Iu) and an adjustable, instantaneous, magnetic trip (red dial) for short circuit protection (8.5 – 14 x Iu). Each dial can be set in accordance with the motor full load current and inrush, making it ideal for installations with varying motor efficiencies. All trip modules have temperature compensation from –5° C (23° F) to +40° C (102° F) and include built-in single phase protection. In the event of an over-current or short-circuit situation, standard ZM trip modules cause the motor protective switch mechanism to open and disconnect power to the load, much like the operation of an inverse time molded case breaker. They make excellent manual motor starters, not only because of their all-in-one design and excellent thermal protection, but because they also provide “close” individual protection from short circuits. Technical Specifications Standard trip module for PKZ2 Adjustable thermal and magnetic trips Includes a manual test feature and tamper-preventive settings cover |